May 22, 2018
 in 
Miscellaneous

Master the monsters with HighPROTEC

H

EARTfelt Welcome, dear friends of protection and control engineering! The generator protection relay MCDGV4 of the HighPROTEC series manufactured by WOODWARD in Germany have long been regarded as reliable and high-precision IED's for the protection of medium-sized generation units. Since the last release now also the phase distance protection with power swing blocking and load blinder as well as the out of step protection were supplemented, meanwhile also large generators are fully covered.

In our current article, we introduce you to the features and highlights of the MCDGV4. At the end of the article, there is a short video, here we provide you an overview of the associated operating software Smart view SE.

What enables the MCDGV4 to manage even high range generators?

First of all, the powerful number of high-precision protection functions, which we will see below. The MCDGV4 leaves nothing to be desired.

Connection example MCDGV4 without block transformer

Enlarged representation of the available ANSI functions of the MCDGV4

Let's see the long list of all supported protection functions and the corresponding ANSI codes:

Protection functions:


21P Phase Distance Protection


24 Overexcitation Protection (Volts per Hertz)


25 Synchronizing or Synchronism-check


27 Undervoltage Protection


32 Directional Power Protection


40 Loss of Excitation / Loss of Field


46 Unbalanced Current Protection



47 Unbalanced Voltage Protection


49 Thermal Protection

50 Overcurrent (instantaneous)


50P Phase Overcurrent (instantaneous)


50N Neutral Overcurrent (instantaneous)


50Ns Sensitive Neutral Overcurrent (instantaneous)

50R Overcurrent residual current


51 Overcurrent


51P Phase Overcurrent


51N Neutral Overcurrent


51Ns Sensitive Neutral Overcurrent

51R Overcurrent resudual current


51C Voltage Controlled Overcurrent (via adaptive Parameters)


51Q Negative Phase Sequence Overcurrent (multiple trip characteristics)


51V Voltage Restrained Overcurrent
55 Power Factor Protection

55 Power Factor Supervision


59 Overvoltage Protection


59TN Third Harmonic Neutral Overvoltage

59A Overvoltage Protection

59N Neutral Overvoltage Protection

64REF Restricted Ground Fault Protection

67  Directional Overcurrent 


67N Directional Neutral Overcurrent


67Ns Sensitive Directional Neutral Overcurrent


67P Directional Phase Overcurrent

67R Directional Overcurrent resudual current

68 Power Swing Blocking



78 Out of Step Tripping


81 Frequency Protection


81U Underfrequency Protection


81O Overfrequency Protection


81R ROCOF (df/dt)


87G Generator Differential Protection


87GP Generator Phase Differential Protection


87GN Generator Ground Differential Protection



87U Unit Differential Protection (protected zone includes generator and step-up transformer)


87UP Unit Phase Differential Protection (protected zone includes generator and step-up transformer)


Supervision functions:

50BF Breaker Failure


60FL Voltage Transformer Supervision


60L Current Transformer Supervision

74TC Trip Circuit Supervision

Optional Supplemental Devices

26 Temperature Supervision (additional RTD Box)

56 Loss of excitation (XE2DC)

64R Rotor Earth Fault Protection
 (XR1)

The mentioned protection functions are all on board in the HighPROTEC series. This major advantage is already in the planning phase of the protection concept to wear, no function points, no consideration of the processor load, no thought in terms of the transformer rated currents: Because even here, the device can later be switched between 1 A and 5 A.

Among the functional highlights of the MCDGV4's

🌐 Comprehensive phase and ground differential protection detects electrical faults within the entire block protection area

🌐 Phase distance protection, two elements

🌐 Power swing blocking

🌐 Out of step tripping

🌐 The overexcitation protection comes along with two elements (e.g. for the protection of the step-up transformer during run up (V/f)

🌐 Six elements (voltage dependent) over-current protection (ANSI / IEC / 51C / 51V) + 4 earth fault elements

🌐 Inadvertent energization detection in order to detect the inadvertent supply of the mains voltage to the generator during standstill

🌐 Negative phase sequence protection e.g. in case of loosing a phase

🌐 Digital integration of analog signals, e.g. Buchholz supervision (up to 24 signals)

🌐 Optional temperature supervision with up to 12 external sensors

🌐 QV protection, Undervoltage-Reactive Power protection

🌐 Considerably frequency protection package: Six elements configurable as f <, f>, df/dt, Vektor Surge

🌐 Synch Check (Generator to mains, mains-to-mains), options e.g. to switch onto dead bus

Also on board:

The MCDGV4 has a 120-second non-volatile fault recorder, a 20-fault recorder, an event recorder for up to 300 events, and the ability to record up to 4000 non-volatile trend records for each channel with 10 channels.

Commissiong is very well supported by WOOWARD. For fault analysis, the MCDGV4 has a very practical fault simulator. This offers the possibility of simulating measured quantities or measured values ​​of currents and voltages. By means of the corresponding submenu, three simulation cycles can be realized:

🌐 Pre-fault

🌐 Failure

🌐 Post-fault State (Phase)

Free programmable logic, time synchronization, IT security and sufficient communication options incl. IEC61850 are mandatory (see also "Unboxing" WOODWARDS MCDGV4).

Smart view | The software tool for all HighPROTEC devices

In the following video we give you an overview of the HighPROTEC operating software Smart view in connection with a MCDGV4.

You have now got a little insight into the software Smart view, in our view, a successful configuration and commissioning tool. We are glad that you have shared your most valuable with us, your time,

until next time,

HEARTfelt Greetings Alexander Muth (👨‍💻)